2001-01-08 00:00:00STORMWATER, WATER AND SANITARY ALREADY
 APPROVED THRU SEPARATE REVIEWS AT ENG.
 SERVICES.SERVIES FOR SW, SS,WILL
 BE INSTALLED VIA HOME DEPOT PLAN.
 SANITATION COMMENTS.APPROVED WITH
 PREVISO: OPENING OF STANDARD TRASH
 ENCLOSURE PLANS, ON PAGE C6 (BOT. RIGHT
 AND TOP RIGHT)DO NOT MATCH. THE GATES
 MUST HAVE A 12' OPENING BETWEEN THE
 GATE POSTS.ADDITIONALLY THE WIDTH OF
 THE OPEN AREA BETWEEN THE CONCRETE WALLS
 IS 22' - 8", IT MUST BE OVER 24' WIDE TO
 TAKE TWO GATES AND TWO GATE POSTS AS
 SHOWN ON THE TOP RIGHT DRAWING OF PAGE
 C6.THE DRAWING ALSO CONFLICTS WITH THE
 DRAWING ON PAGE 2 OF THE BUILDING PLAN
 IT SHOWS ONLY 11' FROM THE CENTER OF THE
 GATE POSTS.