| Plan Review Notes For Permit 99100387 |
| Permit Number |
99100387 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | STORMWATER, WATER AND SANITARY ALREADY | | | APPROVED THRU SEPARATE REVIEWS AT ENG. | | | SERVICES.SERVIES FOR SW, SS,WILL | | | BE INSTALLED VIA HOME DEPOT PLAN. | | | SANITATION COMMENTS.APPROVED WITH | | | PREVISO: OPENING OF STANDARD TRASH | | | ENCLOSURE PLANS, ON PAGE C6 (BOT. RIGHT | | | AND TOP RIGHT)DO NOT MATCH. THE GATES | | | MUST HAVE A 12' OPENING BETWEEN THE | | | GATE POSTS.ADDITIONALLY THE WIDTH OF | | | THE OPEN AREA BETWEEN THE CONCRETE WALLS | | | IS 22' - 8", IT MUST BE OVER 24' WIDE TO | | | TAKE TWO GATES AND TWO GATE POSTS AS | | | SHOWN ON THE TOP RIGHT DRAWING OF PAGE | | | C6.THE DRAWING ALSO CONFLICTS WITH THE | | | DRAWING ON PAGE 2 OF THE BUILDING PLAN | | | IT SHOWS ONLY 11' FROM THE CENTER OF THE | | | GATE POSTS. |
|