Plan Review Notes
Plan Review Notes For Permit 99100289
Permit Number 99100289
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00SHOWERS SHALL COMPLY W/FACBC SEC. 4.21.2
 (THE DIMENSIONS SHALL COMPLY W/FACBC
 FIG.35 (A) OR (B).
  
 SHT.A9.5-LAVATORY CLEARANCES SHALL
 COMPLY W/FACBC SEC.4.19.2.
  
 HEIGHT OF WATER CLOSET SHALL BE 19"AFF
 PER FACBC SEC.4.16.3.
  
 INDICATE THE CORRECT OCCUPANT LOAD PER
 SPC SEC.407.1.3.THE FACILITY DOESN'T
 COMPLY W/TABLE 407 FOR THE MINIMUM
 REQD.FIXTURES AND POTTY PARITY.
  
 PLANS REFER TO PLUMBING SHEET P-4 AND
 SHEET P-4 IS NOT WITH SUBMITTED PLANS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SHT.P-1-8"OVERFLOW DRAINING INTO 6"LINE.
 COMPLY W/SPC SEC.307.5.