2001-01-08 00:00:00SHOWERS SHALL COMPLY FULLY COMPLY
 W/FACBC SEC.4.21.2.(THE DIMENSIONS SHALL
 COMPLY W/FACBC FIG.35 (A) OR (B).
  
 SHOWER CONTROLS SHALL COMPLY W/FACBC
 SEC.4.21.5.CLEARLY SHOW MIN.AND MAX.
 DIMENSIONS.
  
 SHT.A-9.5-LAVATORY CLEARANCES SHALL
 COMPLY W/FACBC 4.19.2
  
 SHOW HEIGHT OF WATER CLOSET PER FACBC
 SEC.4.16.3.
  
 INDICATE THE CORRECT OCCUPANT LOAD PER
 SPC SEC.407.1.3. THE FACILITY DOESN'T
 COMPLY W/TABLE 407 FOR THE MINIMUM REQD.
 FIXTURES.
  
 NO URINALS PERMITTED ON WET VENT PER
 SPC 911.1(2)EXCEPTION.
  
 CIRCUIT AND LOOP SYSTEM IN MEN'S ROOM
 SHALL COMPLY W/SPC SEC.914.1.(VENT REQD.
 IN FRONT OF LAST UPSTREAM FIXTURE DRAIN.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1,610.4.2.
  
 PLANS REFER TO PLUMBING SHEET P-4 AND
 CIVL DRAWINGS.NEITHER HAVE BEEN SUB-
 MITTED.
  
 DESIGNATE ONE SIZE OVERFLOW DRAIN FOR
 THE STORM SYSTEM. (EITHER 6" OR 8")
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).(PROVISIONS SHALL BE
 MADE FOR PERSONS WHO HAVE TROUBLE BEND-
 ING OR STOOPING.