Plan Review Notes
Plan Review Notes For Permit 99100267
Permit Number 99100267
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00THE MINIMUM SIZE OF THE HANDICAP ACCESS-
 IBLE STALL PER FACBC IS 79"(THE PLANS
 SHOW 72") AND SPC SEC.403.1 REQUIRES
 ACCESS FOR CLEANING.(A MIN.OF 2"MUST
 BE PROVIDED BETWEEN WALL AND EDGE OF
 LAV.)
  
 YOU DO NOT SHOW THE REQD.FIXTURE CLEAR-
 ANCES FOR THE HANDICAP FIXTURES.COMPLY
 W/FACBC SECS.4.15,4.17,4.4.18,4.19.
  
 SINK IN GREAT ROOM SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 PROVISIONS SHALL BE MADE AT DRINKING
 FOUNTAIN FOR PERSONS WHO HAVE TROUBLE
 BENDING OR STOOPING PER FACBC SEC.4.1.3.
 (10)(A)