| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT SQUARE FOOTAGE OF BUILDING AND |
| | OCCUPANT LOAD.STRUCTURE SHALL COMPLY |
| | W/SPC TABLE 407 FOR MINIMUM TOILET |
| | FACILITIES.COMPLIANCE W/FLA.STATUTE |
| | 553.141 PARAGRAPH(1).(POTTY PARITY). |
| | |
| | SHT.B-1.HANDICAP STALLS SHALL COMPLY |
| | W/FACBC SEC.4.17.3.(SEE EXCEPTION:NEW |
| | CONSTRUCTION.AND FIGURE 30(A). |
| | |
| | CLEARLY SHOW REQD.MOUNTING HEIGHT |
| | DIMENSIONS AND CLEAR FLOOR SPACE UNDER |
| | PLBG.FIXTURES PER FACBC 1997 EDITION. |
| | |
| | SHOW FIXTURE CLEARANCES PER FACBC AND |
| | SPC SEC.403.4.(SHOW CLEAR FLOOR ACCESS |
| | FOR URINAL.SEE FACBC SEC.4.18.) |
| | |
| | SINK BY GREAT ROOM SHALL COMPLY W/FACBC |
| | SEC.4.24.1- 4.24.7. |
| | |
| | FLOOR DRAIN REQD.IN STAFF TOILET ROOM. |
| | SPC 409.4.1.1. |
| | |
| | WATER HEATER SHALL BE READILY ACCESSIBLE |
| | PER SPC SEC,501.7.- PROVIDE PERMANENT |
| | FIXED LADDER OR PLACE HEATER ON FLOOR. |
| | |
| | HOT WATER SHALL BE VALVED PER SPC SEC. |
| | 610.4.2. |
| | . |
| | DRINKING FOUNTAIN IS NOT SHOWN ON SHT. |
| | P4.1 AND IS NOT SHOWN ON THE WATER OR |
| | SANITARY RISER . |
| | |
| | SUBMIT COPY OF CIVIL DRAWING SHOWING |
| | CONTINUATION OF SANITARY AND WATER LINES |
| | CITY OF WPB AMENDMENTS TO STANDARD PLBG. |
| | CODE SEC.104.2.1. |
| | |
| | DESIGN OF CIRCUIT AND LOOP SYSTEM SHALL |
| | COMPLY W/SPC SEC.914.1,920.3. |
| | |
| | NOTE:THIS IS THE THIRD TIME THIS PLAN |
| | HAS BEEN REVIEWED AND THE COMMENTS ARE |
| | BASICALLY THE SAME EACH TIME.THESE ITEMS |
| | ARE NOT GOING AWAY.MAKE ALL CORRECTIONS |
| | TO THE PLANS PRIOR TO RESUBMITTAL. |