Plan Review Notes
Plan Review Notes For Permit 99100266
Permit Number 99100266
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-02-23 00:00:001) PROVIDE DETAILS ON FIRE HYDRANT
 CONNECTION AND TYPE THAT IS PLANNED.
 ONLY CERTAIN TYPE OF HYDRANTS ALLOWED.
 2) UNDERGROUND FIRE LINES AND HYDRANT
 ARE TO COMPLY WITH NFPA 24, THE
 STANDARD FOR UNDERGROUND FIRE MAINS AND
 THEIR APPURTENANCES.
 3) PLEASE SEE RED-LINED COMMENTS ON
 PLANS FOR FURTHER ISSUES.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910