| Plan Review Notes For Permit 99100264 |
| Permit Number |
99100264 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ON SEPTEMBER 27,2000, WRITER EXAMINED | | | PLANS FOR THE FIRE ALARM SYSTEM | | | SUBMITTED BY TYPHOON SERVICES. | | | 1) NO CUT SHEETS FOR FIRE ALARM DEVICES | | | PLANNED FOR USE WERE PROVIDED. | | | 2) FIRE ALARM SYSTEM TO BE CLASS A OR | | | ADDRESSABLE. | | | 3) PLANS DISPLAY MANUAL PULL STATIONS | | | ONLY AT THE FIRST FLOOR LEVEL. A REVIEW | | | OF THE LIFE SAFETY CODE, REQUIRES | | | MANUAL PULL STATIONS NEAR EACH REQUIRED | | | EXIT. | | | 4) FIRE ALARM SYSTEMS TO BE MONITORED | | | BY A UL LISTED CENTRAL STATION. |
|