Plan Review Notes
Plan Review Notes For Permit 99100264
Permit Number 99100264
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00ON SEPTEMBER 27,2000, WRITER EXAMINED
 PLANS FOR THE FIRE ALARM SYSTEM
 SUBMITTED BY TYPHOON SERVICES.
 1) NO CUT SHEETS FOR FIRE ALARM DEVICES
 PLANNED FOR USE WERE PROVIDED.
 2) FIRE ALARM SYSTEM TO BE CLASS A OR
 ADDRESSABLE.
 3) PLANS DISPLAY MANUAL PULL STATIONS
 ONLY AT THE FIRST FLOOR LEVEL. A REVIEW
 OF THE LIFE SAFETY CODE, REQUIRES
 MANUAL PULL STATIONS NEAR EACH REQUIRED
 EXIT.
 4) FIRE ALARM SYSTEMS TO BE MONITORED
 BY A UL LISTED CENTRAL STATION.