| Plan Review Notes For Permit 99100227 |
| Permit Number |
99100227 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************* | | | | | | 1)NOTE: NEED TO SUBMIT REVISED RISER | | | LOAD CALCULATION. TO INCLUDE DISPLAY | | | LIGHTING LOAD AS A CONTINUOUS LOAD. | | | FIGURED AT 125% AS PER ART;220-3A | | | | | | PLEASE HAVE THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL BEFORE ROUGH | | | ELECTRICAL INSPECTION. |
|