| Plan Review Notes For Permit 99100167 |
| Permit Number |
99100167 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO***************** | | | | | | 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | SMOKE DETECTOR REQ`D OUTSIDE BEDROOM #2 | | | ALSO SMOKE DETECTOR NEEDS TO BE IN THE | | | IMMEDIATE VICINITY OUTSIDE BEDROOM #3. | | | 2)NOTE: AS PER ART:210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTER/ISLAND ARE TO BE | | | GFI/GFI PROTECTED. | | | 3)NOTE:NEED TO REVISERISER DIAGRAM | | | SHOWINGSEPARATE FEEDS TO MAIN DISC.`S | | | AS PER ART:373-8 PANELS/DISC. ARE NOT TO | | | BE USED AS RACEWAYS. | | | | | | PLEASE HAVE THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL BEFORE FIRSR ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. |
|