| Plan Review Notes For Permit 99100121 |
| Permit Number |
99100121 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ******************PROVISO************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF D | | | EQUIPMENT BEING INSTALLED AND BRANCH | | | BREAKERS. AIC RATING IS FIGURED FROM | | | FAULT CURRRENT CALCULATIONS. AS PER ARTS | | | 110-9/215-5 | | | 2)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS OF | | | RESIDENTIAL DWELLINGS OF NEW | | | CONSTRUCTION. | | | 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. ALSO ALL OTHER OUTLET | | | -S WITHIN 6` OF SINK( SEE OUTLET CIRCLED | | | ON WALL KITCHEN/LIVING ROOM. | | | 4)NOTE:AS PER 210-52D BATH REQ`S A 20AMP | | | DEDICATED CIRCUT AND TO BE #12 AWG. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL BEFORE FIRST | | | ROUGH ELECTRICAL INSPECTION. |
|