Plan Review Notes
Plan Review Notes For Permit 99100121
Permit Number 99100121
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00******************PROVISO**************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF D
 EQUIPMENT BEING INSTALLED AND BRANCH
 BREAKERS. AIC RATING IS FIGURED FROM
 FAULT CURRRENT CALCULATIONS. AS PER ARTS
 110-9/215-5
 2)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS OF
 RESIDENTIAL DWELLINGS OF NEW
 CONSTRUCTION.
 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED. ALSO ALL OTHER OUTLET
 -S WITHIN 6` OF SINK( SEE OUTLET CIRCLED
 ON WALL KITCHEN/LIVING ROOM.
 4)NOTE:AS PER 210-52D BATH REQ`S A 20AMP
 DEDICATED CIRCUT AND TO BE #12 AWG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION.