| Plan Review Notes For Permit 99100118 |
| Permit Number |
99100118 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO****************** | | | | | | 1)NOTE:AS PER ARTS:110-9/215-5 NEED TO | | | SUBMIT AIC RATING OF EQUIPMENT/MAINS/ | | | BREAKERS. AIC RATING IS FIGURED FROM | | | FAULT CURRENT CALCULATIONS. | | | 2)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 3)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS OF NEW | | | CONSTRUCTION OF RESIDENTIAL DWELLINGS. | | | 4)NOTE:PLEASE NOTE THAT ON PANEL SCHED. | | | AS PER ART;210-52D BATH RECEPTS. ARE TO | | | BE ON A SEPARATE 20AMP. CIRCURT. | | | | | | NED TO HAVE ALL THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. |
|