2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE:AS PER ARTS:110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT/MAINS/
 BREAKERS. AIC RATING IS FIGURED FROM
 FAULT CURRENT CALCULATIONS.
 2)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 3)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS OF NEW
 CONSTRUCTION OF RESIDENTIAL DWELLINGS.
 4)NOTE:PLEASE NOTE THAT ON PANEL SCHED.
 AS PER ART;210-52D BATH RECEPTS. ARE TO
 BE ON A SEPARATE 20AMP. CIRCURT.
  
 NED TO HAVE ALL THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.