| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-PLEASE REVISE ALL ORIGINAL DRAWINGS |
| | SHOWING ALL CORRECTIONS REQUESTED ON |
| | PLANS. |
| | 2-REVISE FOOTING F-2. SEE RECOMMENDATION |
| | ON SOIL TEST REPORT FOR MINIMUM SIZE |
| | OF CONTINUOUS FOOTING. MIN. DEPTH OF |
| | F-2 TO BE 16" AS PER SEC 1804.1.3 SBC |
| | 1997 AND 1804.1.9 CITY AMENDMENTS. |
| | 3-PROVIDE PRODUCT APPROVAL FOR: ENTRY |
| | DOORS WITH SIDELITES ASSEMBLY, WINDOW |
| | AND DOOR MULLIONS, ROOF TILE, GARAGE |
| | DOOR. |
| | NOTE: NORANDEX PRODUCT APPROVALS ARE |
| | NOT ACCEPTED UNLESS THEY PROVIDE SITE |
| | SPECIFIC COMPLETE ENGINEERING CALCS |
| | AND SPECIFICATIONS OR APPROVED PRODUCT |
| | APPROVAL. |
| | 4-STORM PANELS: |
| | -INSTALLATION SCHEDULE, KEY PLAN AND |
| | ENGINEER FLOOR PLANS DON'T MATCH. |
| | -PROVIDE COMPLETE INSTALLATION SCHEDULE |
| | AS PER CITY SAMPLE, ATTACHED. |
| | 5-PROVIDE SAFETY GLASS AS REQUIRED. SEE |
| | PLANS FOR COMMENTS. SEC 2405.2 SBC/97. |
| | 6-MASTER BEDROOM OPTION OF HAVING 34/5 |
| | SINGLE HUNG WINDOW (SHEET A-2) DOESN'T |
| | MEET THE MINIMUM EGRESS REQUIREMENTS. |
| | REVISE AS REQ'D. SEC 1005.4.4 SBC/97. |
| | 7-UPDATE ALL ENGINEERED TRUSSES: |
| | -REVISE MEAN ROOF HEIGHT. |
| | -DESIGN CRITERIA ACCEPTED BY THIS |
| | OFFICE IS SBC 1997 OR ASCE 7-95 AND |
| | MUST BE INCORPORATED IN THE ENGINEERED |
| | TRUSSES. |
| | 8-PROVIDE COMPLETE SECTION/DETAIL AT |
| | MIDDLE BEARING POINT OF TRUSS D-16. |
| | SPECIFY ALL CONNECTORS (TOP & BOTTOM) |
| | AND COLUMN. SEC 104.2.2 CITY AMENDMENT |
| | 9-PROVIDE COMPLETE BUCK DETAILS FOR ALL |
| | EXTERIOR WINDOW TYPES, DOOR TYPES AND |
| | GARAGE DOOR.SEC 104.2.2 CITY AMENDMENT |
| | 10-NOTE: |
| | FLOOD ZONE "A-8". PROVIDE ELEVATION |
| | CERTIFICATE. |