Plan Review Notes
Plan Review Notes For Permit 99100116
Permit Number 99100116
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PLEASE REVISE ALL ORIGINAL DRAWINGS
 SHOWING ALL CORRECTIONS REQUESTED ON
 PLANS.
 2-REVISE FOOTING F-2. SEE RECOMMENDATION
 ON SOIL TEST REPORT FOR MINIMUM SIZE
 OF CONTINUOUS FOOTING. MIN. DEPTH OF
 F-2 TO BE 16" AS PER SEC 1804.1.3 SBC
 1997 AND 1804.1.9 CITY AMENDMENTS.
 3-PROVIDE PRODUCT APPROVAL FOR: ENTRY
 DOORS WITH SIDELITES ASSEMBLY, WINDOW
 AND DOOR MULLIONS, ROOF TILE, GARAGE
 DOOR.
 NOTE: NORANDEX PRODUCT APPROVALS ARE
 NOT ACCEPTED UNLESS THEY PROVIDE SITE
 SPECIFIC COMPLETE ENGINEERING CALCS
 AND SPECIFICATIONS OR APPROVED PRODUCT
 APPROVAL.
 4-STORM PANELS:
 -INSTALLATION SCHEDULE, KEY PLAN AND
 ENGINEER FLOOR PLANS DON'T MATCH.
 -PROVIDE COMPLETE INSTALLATION SCHEDULE
 AS PER CITY SAMPLE, ATTACHED.
 5-PROVIDE SAFETY GLASS AS REQUIRED. SEE
 PLANS FOR COMMENTS. SEC 2405.2 SBC/97.
 6-MASTER BEDROOM OPTION OF HAVING 34/5
 SINGLE HUNG WINDOW (SHEET A-2) DOESN'T
 MEET THE MINIMUM EGRESS REQUIREMENTS.
 REVISE AS REQ'D. SEC 1005.4.4 SBC/97.
 7-UPDATE ALL ENGINEERED TRUSSES:
 -REVISE MEAN ROOF HEIGHT.
 -DESIGN CRITERIA ACCEPTED BY THIS
 OFFICE IS SBC 1997 OR ASCE 7-95 AND
 MUST BE INCORPORATED IN THE ENGINEERED
 TRUSSES.
 8-PROVIDE COMPLETE SECTION/DETAIL AT
 MIDDLE BEARING POINT OF TRUSS D-16.
 SPECIFY ALL CONNECTORS (TOP & BOTTOM)
 AND COLUMN. SEC 104.2.2 CITY AMENDMENT
 9-PROVIDE COMPLETE BUCK DETAILS FOR ALL
 EXTERIOR WINDOW TYPES, DOOR TYPES AND
 GARAGE DOOR.SEC 104.2.2 CITY AMENDMENT
 10-NOTE:
 FLOOD ZONE "A-8". PROVIDE ELEVATION
 CERTIFICATE.