Plan Review Notes
Plan Review Notes For Permit 99100116
Permit Number 99100116
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-PLEASE REVISE ALL ORIGINAL DRAWINGS
 SHOWING ALL THE CORRECTIONS/
 CLARIFICATIONS REQUESTED ON PLANS.
 2-REVISE FOOTING F-2. SEE RECOMMENDATION
 ON SOIL TEST REPORT FOR MINIMUM SIZE
 OF CONTINUOUS FOOTINGS. REVISE DWG.
 3-PROVIDE PRODUCT APPROVAL FOR: ENTRY
 DOORS WITH SIDELITES ASSEMBLY, WINDOW
 AND DOOR MULLIONS, ROOF TILE, GARAGE
 DOOR.
 NOTE: NORANDEX PRODUCT APPROVALS ARE
 NOT ACCEPTED UNLESS THEY PROVIDE SITE
 SPECIFIC COMPLETE ENGINEERING
 CALCULATIONS OR APPROVED PRODUCT
 APPROVAL.
 4-STORM PANELS:
 -INSTALLATION SCHEDULE, KEY PLAN AND
 ENGINEER FLOOR PLANS DON'T MATCH.
 REVISE AS REQUIRED.
 5-PROVIDE SAFETY GLASS AS REQUIRED. SEE
 PLANS FOR COMMENTS.SEC 2405.2 SBC 1997
 6-MASTER BEDROOM OPTION OF HAVING 34/5
 SINGLE HUNG WINDOW (SHEET A-2) DOESN'T
 MEET THE MINIMUM EGRESS REQUIREMENTS
 SEC. 1005.4.4 SBC 1997.
 7-UPDATE ALL ENGINEERED TRUSSES:
 -REVISE MEAN ROOF HEIGHT.SEE ELEVATIONS
 -DESIGN CRITERIA ACCEPTED BY THIS
 OFFICE IS SBC 1997 OR ASCE 7-95 AND
 MUST BE INCORPORATED IN THE ENGINEERED
 TRUSSES (CUT AND PASTE JOB WILL NOT BE
 ACCEPTED).
 8-PROVIDE COMPLETE SECTION/DETAIL AT
 MIDDLE BEARING POINT OF TRUSS D-16.
 SPECIFY ALL CONNECTORS (TOP & BOTTOM)
 SEC. 104.2.2 CITY AMENDMENTS.
 NOTE: ENGINEERED TRUSS DRAWING D-16
 CALLS FOR A BEARING SIZE OF 5".8.CHECK
 9-PROVIDE COMPLETE BUCK DETAILS FOR ALL
 EXTERIOR WINDOW TYPES, ALL EXTERIOR
 DOOR TYPES AND GARAGE DOOR.
 10-NOTE:
 FLOOD ZONE A8. PROVIDE ELEVATION
 CERTIFICATE.
 11-PAY IMPACT FEES TO THE COUNTY.
 12-OWES $25.36 TO CITY FOR RADON FEES.