Plan Review Notes
Plan Review Notes For Permit 99100116
Permit Number 99100116
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO*****************
  
 1)NOTE: AS PER ARTS:110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT BEING
 INSTALLED AND BRANCH BREAKERS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED. AND ALL OTHER OUTLETS
 WITHIN 6`.
 3)AS PER ART:210-52D BATH CICUTS ARE
 REQ`D TO BE 20AMP WITH #12 AWG AND TO BE
 DEDICATED FOR ONLY BATH RECEPTS.
 4)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS IN DWELLINGS
 OF NEW CONSTRUCTION.
  
 NEED TO SUBMIT THE ABOVE FOR REVIEW AND
 APPROVAL BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION.