| Plan Review Notes For Permit 99100116 |
| Permit Number |
99100116 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO***************** | | | | | | 1)NOTE: AS PER ARTS:110-9/215-5 NEED TO | | | SUBMIT AIC RATING OF EQUIPMENT BEING | | | INSTALLED AND BRANCH BREAKERS. | | | AIC RATING IS FIGURED FROM FAULT CURRENT | | | CALCULATIONS. | | | 2)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. AND ALL OTHER OUTLETS | | | WITHIN 6`. | | | 3)AS PER ART:210-52D BATH CICUTS ARE | | | REQ`D TO BE 20AMP WITH #12 AWG AND TO BE | | | DEDICATED FOR ONLY BATH RECEPTS. | | | 4)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS IN DWELLINGS | | | OF NEW CONSTRUCTION. | | | | | | NEED TO SUBMIT THE ABOVE FOR REVIEW AND | | | APPROVAL BEFORE FIRST ROUGH ELECTRICAL | | | INSPECTION. |
|