Plan Review Notes
Plan Review Notes For Permit 99100076
Permit Number 99100076
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00THE NUMBER AND TYPE OF REQD.PLUMBING
 FIXTURES SHALL COMPLY W/SPC TABLE 407.
  
 OCCUPANT LOAD SHALL BE BASED ON SQUARE
 FOOTAGE OF HABITABLE FLOOR SPACE PER SPC
 SEC.407.1.3.
  
 SHT.M-1.-LOOP VENT SHALL REMAIN 1/2 PIPE
 SIZE OF HORIZONTAL WASTE LINE.(3" VTR.)
  
 HOSE BIBBS SHALL BE VALVED PER SPC
 610.4.1.
  
 WATER TREATMENT UNIT SHALL BE NSF
 APPROVED PER SPC SEC.615.1.
  
 EMERGENCY PAN DRAIN SHALL DISCHARGE TO
 AN OBSERVABLE POINT.REFER TO MECH.CODE.