| Plan Review Notes For Permit 99100076 |
| Permit Number |
99100076 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | THE NUMBER AND TYPE OF REQD.PLUMBING | | | FIXTURES SHALL COMPLY W/SPC TABLE 407. | | | | | | OCCUPANT LOAD SHALL BE BASED ON SQUARE | | | FOOTAGE OF HABITABLE FLOOR SPACE PER SPC | | | SEC.407.1.3. | | | | | | SHT.M-1.-LOOP VENT SHALL REMAIN 1/2 PIPE | | | SIZE OF HORIZONTAL WASTE LINE.(3" VTR.) | | | | | | HOSE BIBBS SHALL BE VALVED PER SPC | | | 610.4.1. | | | | | | WATER TREATMENT UNIT SHALL BE NSF | | | APPROVED PER SPC SEC.615.1. | | | | | | EMERGENCY PAN DRAIN SHALL DISCHARGE TO | | | AN OBSERVABLE POINT.REFER TO MECH.CODE. |
|