| 2001-01-08 00:00:00 | ************* PROVISO******************* | | | | | | 1)NOTE:PLEASE CORRECT SIZE OF EQUIPMENT | | | GROUNDING CONDUCTOR. SIZE AS REQ`D BY | | | ART;250-95 OF THE NEC. | | | | | | 2)NOTE: PLEASE SUBMIT MORE DETAILED | | | GROUNDING SYSTEM. TO INCLUDE ANY GROUND- | | | ING PLATES BEING USED. | | | PLEASE SHOW,,,,GROUNDING ELECTRODE | | | CONDUCTOR GOING TO ALL THE MEANS OF | | | GROUNDING. TO INCLUDE GROUND RODS(S), | | | BLDG.STEEL,AND COLD WATER PIPE. ALL | | | AS PART OF THE SYSTEM. AS REQ`D BY ART; | | | 250-81 AND 215-5 OF THE NEC. | | | PLEASE SHOW GROUNDING THAT IS BEING | | | REQ`D FOR TELEPHONE AND COMPUTER SYSTEMS | | | | | | PLEASE HAVE ALL THE ABOVE INFORMATION | | | SUBMITTED FOR REVIEW AND APPROVAL | | | BEFORE ANY ELECTRICAL INSPECTION IS | | | CALLED IN.IF THERE ARE ANY QUESTIONS; | | | CALL 659-8096 EXT 8372 |
|