2001-01-08 00:00:00************* PROVISO*******************
  
 1)NOTE:PLEASE CORRECT SIZE OF EQUIPMENT
 GROUNDING CONDUCTOR. SIZE AS REQ`D BY
 ART;250-95 OF THE NEC.
  
 2)NOTE: PLEASE SUBMIT MORE DETAILED
 GROUNDING SYSTEM. TO INCLUDE ANY GROUND-
 ING PLATES BEING USED.
 PLEASE SHOW,,,,GROUNDING ELECTRODE
 CONDUCTOR GOING TO ALL THE MEANS OF
 GROUNDING. TO INCLUDE GROUND RODS(S),
 BLDG.STEEL,AND COLD WATER PIPE. ALL
 AS PART OF THE SYSTEM. AS REQ`D BY ART;
 250-81 AND 215-5 OF THE NEC.
 PLEASE SHOW GROUNDING THAT IS BEING
 REQ`D FOR TELEPHONE AND COMPUTER SYSTEMS
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE ANY ELECTRICAL INSPECTION IS
 CALLED IN.IF THERE ARE ANY QUESTIONS;
 CALL 659-8096 EXT 8372