2001-01-08 00:00:00***************DENIED******************
  
 1)NOTE:ELECTRICAL RISER DIAGRAM IS NOT
 CORRECT!!! MAIN CIRCUT BREAKER PANEL
 IS REQ`D OR MAIN DISC. YOU SHOW MAIN
 LUG ONLY AND NO FORM OF MAIN DISC.
 2)NOTE;ALSO GROUNDING ELECTRODE
 CONDUCTOR IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISC. YOU SHOW GRND.
 BEING INSTALLED FROM METER TO PANEL????
 3)NOTE:AS PER 250-81MORE THAN ONE
 GROUNDING ELECTRODE IS REQ`D.
 4)NOTE;LOAD CALCULATIONS ARE NOT CORRECT
 LOAD CANNOT BE DERATED FOR CONTINOUS
 LIGHTING LOAD.!!!
 PLEASE DOUBLE CHECK TRAILER FOR OTHER
 LOADS ;;;SUCH AS AIR CONDITIONING,FRIG,
 HOT WATER HEATER ETC.LEASING TRAILER
 WOULD MOST LIKELY HAVE A/C.
 PLEASE REDO LOAD CALCS.
  
 ALL THE ABOVE MUST BE DONE AND SUBMITTED
 FOR REVIEW AND APPROVAL.
 THE ABOVE FALLS UNDER ART;215-5