| Plan Review Notes For Permit 99100065 |
| Permit Number |
99100065 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************DENIED****************** | | | | | | 1)NOTE:ELECTRICAL RISER DIAGRAM IS NOT | | | CORRECT!!! MAIN CIRCUT BREAKER PANEL | | | IS REQ`D OR MAIN DISC. YOU SHOW MAIN | | | LUG ONLY AND NO FORM OF MAIN DISC. | | | 2)NOTE;ALSO GROUNDING ELECTRODE | | | CONDUCTOR IS ONLY INSTALLED AFTER THE | | | FIRST MEANS OF DISC. YOU SHOW GRND. | | | BEING INSTALLED FROM METER TO PANEL???? | | | 3)NOTE:AS PER 250-81MORE THAN ONE | | | GROUNDING ELECTRODE IS REQ`D. | | | 4)NOTE;LOAD CALCULATIONS ARE NOT CORRECT | | | LOAD CANNOT BE DERATED FOR CONTINOUS | | | LIGHTING LOAD.!!! | | | PLEASE DOUBLE CHECK TRAILER FOR OTHER | | | LOADS ;;;SUCH AS AIR CONDITIONING,FRIG, | | | HOT WATER HEATER ETC.LEASING TRAILER | | | WOULD MOST LIKELY HAVE A/C. | | | PLEASE REDO LOAD CALCS. | | | | | | ALL THE ABOVE MUST BE DONE AND SUBMITTED | | | FOR REVIEW AND APPROVAL. | | | THE ABOVE FALLS UNDER ART;215-5 |
|