2001-01-08 00:00:00REJECTED;
 1.DOLLAR VALUE OF WORK NOT HIGH ENOUGH.
 EQUIPMENT, DUCTS, AND LABOR COSTS MUST
 BE COMBINED F0R TOTAL COST OF JOB.
 2.TWO SETS OF DRAWINGS ARE REQUIRED
 SHOWING AS SMC 104.2.1
 A.MODEL NUMBERS OF CONDENSOR AND
 AIR HANDLER.
 B.SEER VALUE OF THE CONDENSOR.
 C.ALL DUCT WORK MUST BE SIZED
 WITH VENT SIZES.
 D.CFM (CUBIC FEET OF AIR PER.
 MINUTE) FOR EACH DROP.
 03-13-00 I CLYDE LEFT MESSAGE THAT MECH.
 PLANS REQUIRED.
 03-16-00 SPOKE TO ANTONIO PIERRE INFORM
 HIM OF THE NOTES AND HE NEEDS
 GET IT YO THE DEPARTMENT.
 *******INFORMED BILL STAPLES OF THIS
 SITUATION AND HE TOLD ME TO
 GET A LETTER TO ANTONIO, THAT
 HE HAS TEN(10) DAYS TO COMPLY
 TO THE CODE.