| 2001-01-08 00:00:00 | ***************PROVISO***************** | | | | | | 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO | | | SUBMIT AIC RATING OF MAINS AND BRKRS. | | | AIC RATING IS FIGURED FROM FAULT CURRENT | | | CALCULATIONS. | | | 2)NOTE:AS PER ART:215-5 NEED TO HAVE | | | RISER DIAGRAM CORRELATE WITH PANEL SCHED | | | RISER DIAGRAM SHOWS MLO PANEL??NEED MAIN | | | DISC. OR MAIN BRKR PANEL WHICH IS WHAT | | | PANEL SCHEDULE SHOWS. | | | ALSO EQUIPMENT GROUND IS ONLY USED AFTER | | | FIRST MEANS OF DISC. | | | 3)NOTE:AS PER ART;250-81 NEED TO SHOW | | | GROUNDING CONDUCTOR ON PANEL SCHEDULE | | | GOING TO COLD WATER PIPE AND BLDG.STEEL | | | ALSO. | | | 4)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | 5)NOTE:PLEASE DRAW IN A/C COND. AND | | | THE FOLLOWING:REQ`D BY CODE.ART;440-11 | | | A/C DISC. AND WP GFI AS PER 210-63 | | | | | | NEED TO HAVE THE ABOVE SUBMITTED FOR | | | REVIEW AND AND APPROVAL BEFORE FIRST | | | ROUGH ELECTRICAL INSPECTION. |
|