Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 SUBMIT AIC RATING OF MAINS AND BRKRS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:AS PER ART:215-5 NEED TO HAVE
 RISER DIAGRAM CORRELATE WITH PANEL SCHED
 RISER DIAGRAM SHOWS MLO PANEL??NEED MAIN
 DISC. OR MAIN BRKR PANEL WHICH IS WHAT
 PANEL SCHEDULE SHOWS.
 ALSO EQUIPMENT GROUND IS ONLY USED AFTER
 FIRST MEANS OF DISC.
 3)NOTE:AS PER ART;250-81 NEED TO SHOW
 GROUNDING CONDUCTOR ON PANEL SCHEDULE
 GOING TO COLD WATER PIPE AND BLDG.STEEL
 ALSO.
 4)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 5)NOTE:PLEASE DRAW IN A/C COND. AND
 THE FOLLOWING:REQ`D BY CODE.ART;440-11
 A/C DISC. AND WP GFI AS PER 210-63
  
 NEED TO HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION.