Plan Review Notes
Plan Review Notes For Permit 99100040
Permit Number 99100040
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00THE ARCHITECT & ENGINEERING PLANS NEED
 THERE ORGINAL SIGNATURE ON EACH PLAN.
  
 THE FRONT ENTRY DOOR IS REQUIRED TO
 PROVIDE 32" CLEAR OPENING WHEN ONE LEAF
 IS OPENED.ATTACHED IS A COPY OF THE
 SBCCI INTERPERTATION WHICH THE BUILDING
 OFFICIALS SUPPORTS. PLANS NEED TO BE
 REVISED.
  
 PROVIDE ATTIC ACESS TO THE LOW ROOF
 WHICH IS LOCATED OVER THE KITCHEN AREA.
  
 SPECIFY AND LOCATE ON THE PLANS THE
 BEARING WALLS AND COLUMNS, STUD SPACING.
  
 SPECIFY ON THE WALL SECTION THE STUCCO
 THICKNESS,INTERIOR WALL FINISH, FURRING
 SPACE, CEILING FINISH, FOOTER RECESS
 DIMENSION, ROOF UNDERLAYMENT FELT PAPER,
 ROOF FINISH AND ATTACHMENT.
  
 THE TRUSSLAYOUT FROM THE TRUSS COMPANY
 SPECIFYS THAT FG2 TRUSS HAS A CONNECTION
 WITH A 11,311LBS.PROVIDE THE CONNECTIO
 DETAIL.
  
 PROVIDE ALL ENGINEERING DETAILS WHICH
 WERE PROVIDED WITH THE PLANS FOR LOT 10.
  
 THE LEFT RIGHT ELEVATION EXCEEDS THE
 PERCENTAGE OF OPENINGS ALLOWED BY TABLE
 600.WALL AREA IS AS FOLLOWS:
 12 X 10= 120SF
 7'6" X 18= 135SF
 255SF X 40 %=102SF ALLOWED
 WALL OPENINGS8X8=64SF
 6X8=48
 2X2=4
 116-102=14SF OVER ALOW
  
 ATTACHED IS A COPY OF THE REVISED
 DESIGN COMPLIANCE FORM WHICH NEEDS TO
 BE COMPLETED.
  
 NEEDS COUNTY IMPACT FEES PAID.