Plan Review Notes
Plan Review Notes For Permit 99100040
Permit Number 99100040
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:THE RISER DIAGRAM SHOWS (MLO)
 PANELS, NEED TO SHOW THEM AS (MCB)
 PANELS,AS SOME FORM OF MAIN DISC.IS REQ`
 ALSO EQUIPMENT GROUND IS SHOWN FROM
 METER TO PANEL,,,,EQUIPMENT GROUND IS
 ONLY TO BE INSTALLED AFTER FIRST MEANS
 OF DISC.ALL THE ABOVE PER 215-5
 2)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR IS REQ`D TO GO TO
 COLD WATER PIPE AND BLDG.STEEL.PLEASE
 SHOW.AS PER 215-5
 3)NOTE;AS PER 110-9/215-5 NEED TO SUBMIT
 AIC RATING OF EQUIPMENT:TO INCLUDE MAINS
 AND BRANCH CIRCUT BRKRS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS
 4)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTOR IS REQ`D OUTSIDE ALL
 SLEEPING ROOMS IN RESIDENTIAL DWELLINGS.
 5)NOTE:NEED TO SHOW A/C EQUIPMENT TO
 INCLUDE DISC.AS PER 440-11 AND REQ`D
 WP GFI RECEPT. PER 210-63
  
 NEED TO HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION.