| Plan Review Notes For Permit 99100040 |
| Permit Number |
99100040 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO***************** | | | | | | 1)NOTE:THE RISER DIAGRAM SHOWS (MLO) | | | PANELS, NEED TO SHOW THEM AS (MCB) | | | PANELS,AS SOME FORM OF MAIN DISC.IS REQ` | | | ALSO EQUIPMENT GROUND IS SHOWN FROM | | | METER TO PANEL,,,,EQUIPMENT GROUND IS | | | ONLY TO BE INSTALLED AFTER FIRST MEANS | | | OF DISC.ALL THE ABOVE PER 215-5 | | | 2)NOTE:AS PER ART;250-81 GROUNDING | | | ELECTRODE CONDUCTOR IS REQ`D TO GO TO | | | COLD WATER PIPE AND BLDG.STEEL.PLEASE | | | SHOW.AS PER 215-5 | | | 3)NOTE;AS PER 110-9/215-5 NEED TO SUBMIT | | | AIC RATING OF EQUIPMENT:TO INCLUDE MAINS | | | AND BRANCH CIRCUT BRKRS. AIC RATING IS | | | FIGURED FROM FAULT CURRENT CALCULATIONS | | | 4)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | SMOKE DETECTOR IS REQ`D OUTSIDE ALL | | | SLEEPING ROOMS IN RESIDENTIAL DWELLINGS. | | | 5)NOTE:NEED TO SHOW A/C EQUIPMENT TO | | | INCLUDE DISC.AS PER 440-11 AND REQ`D | | | WP GFI RECEPT. PER 210-63 | | | | | | NEED TO HAVE THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL BEFORE FIRST | | | ROUGH ELECTRICAL INSPECTION. |
|