Plan Review Notes
Plan Review Notes For Permit 99091140
Permit Number 99091140
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-ENGINEERED TRUSS DRAWINGS NEED TO BE
 UPDATED TO REFLECT SBC 1997.
 ALTERNATIVE: ASCE-95.
 2-THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING. TABLE 1606.2A SBC/97.
 REVISE ENGINEERED TRUSSES AS REQUIRED.
 MEAN ROOF HEIGHT 19'-0" PLUS OR MINUS.
 3-ENGINEERED TRUSSES TO BE MANUALLY
 SIGNED, NOT RUBBER STAMPED.
 4-ARCHITECT OF RECORD TO REVIEW ALL
 TRUSS DRAWINGS PRIOR TO SUBMITTAL TO
 THIS OFFICE.
  
 NOTE:
 CHECK/REVISE ALL UPLIFT CONNECTOR
 SPECIFIED TO ASCERTAIN THAT THEY WILL
 RESIST THE UPLIFT LOADS CALCULATED ON
 THE ENGINEERED TRUSSES.