Plan Review Notes
Plan Review Notes For Permit 99091140
Permit Number 99091140
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE; AS PER ARTS:110-9/215-5 NEEED TO
 SUBMIT AIC RATING OF EQUIPMENT,MAINS AND
 BRKRS.AIC RATING IS DERIVED FROM FAULT
 CURRENT CALCULATIONS.
 2)NOTE:NEED TO HAVE GROUND RODS INCLUDED
 AS APART OF THE GROUNDING ELECTRODE
 SYSTEM ON THE RISER DIAGRAM. 215-5
  
 NEED TO HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION.