2001-01-08 00:00:00COMMENTS BY MANNY GONZALEZ AS PROVISOS
 1. SAMPLE POINT NEEDED AT METER
 2. ON CROSSING 3 AN 18" VERTICAL CLEARAN
 CE REQUIRED BETWEEN WATER AND SANITARY
 3. SHOW PROPOSED SEWER LINE BOLDER
 4. REVISE ALL CROSSINGS TO REFLECT THE
 PROPER PIPE SIZE
 APPROVED WITH PROVISOS
 I HAVE NOTIFIED PETER VANRENZ
 AT KIMLEY HORN TO SUBMITT TRASH
 ENCLOUSURE AND DETAILS.
  
 THE STORM SEWER WAS REVIEWED ON THE
 OVER ALL HOME DEPOT SITE PROJECT
  
 SANITATION:
 NO DUMPSTER ENCLOSURE SHOWN. STATE IF IT
 IS TO BE CITY PICK UP OR PRIVATE.IF
 CITY PICKUP THEN THE FOLLOWING
 REQUIREMENTS MUST BE MET; DUMPSTER MUST
 HAVE A MINIMUM OF 12' OPENING BETWEEN
 THE GATE POSTS.INTERIOR DIMENSIONS OF
 THE ENCLOSURE MUST BE A MINIMUM OF 12'
 WIDE AND 12' DEEP.A CONCRETE PARKING
 STOP BAR MUST BE CENTERED (FROM GATES)
 AND INSTALLED 18" FROM THE BACK WALLED.
 STEEL BARS WILL BE DRILLED OR THRU THE
 STOP BAR AND INTO THE INTERIOR FLOOR OF
 THE ENCLOSURE TO STOP THE BAR FROM MOVIN
 WHEN THE DUMPSTER IS SET INSIDE. THE
 OPENING OF THE DUMPSTER ENCLOSURE MUST
 BE PLACED SO THAT A 40' LONG TRUCK WITH
 THE FORKS EXTENDED CAN APPROACH THE
 OPENING AND PICK UP THE DUMPSTER WITHOUT
 TURNING A SHARP TURN. NOTHING MAY BE
 PLACED OVERHEAD IN THE AREA WHERE THE
 DUMPSTER ENCLOSURE IS SO THAT WHEN THE
 DUMPSTER IS PICKED UP AND DUMPED THE
 DUMPSTER NOR THE TRUCK OR TRUCK FORKS
 WILL BE IMPEDED.