2001-01-08 00:00:00CLEARLY SHOW LOCATION OF GREASE
 INTERCEPTOR ON PLANS.SPC 104.2.1.
  
 CONTACT RODNEY COMPO AT CITY OF W.P.B.
 REGIONAL WASTEWATER TREATMENT PLANT FOR
 GREASE TRAP REQS.(561)835-7423.
  
 MULTIPLE CONDENSATE DRAINS SHALL BE
 SIZED PER STD.MECH.CODE SEC.304.8.4.
  
 RECEPTACLES FOR INDIRECT WASTES SHALL BE
 FLOOR DRAINS OR FLOOR SINKS PER SPC SEC.
 807.
  
 CLEARLY SHOW TERMINATION PT.OF TRENCH
 DRAIN AT CAR WASH.SPC 104.2.1.
  
 VENTING FOR SANITARY SYSTEM SHALL COMPLY
 W/SPC SEC.920.2.
  
 SPACING FOR COPPER TUBE SHALL BE 10'MAX.
 FOR SIZES 2" AND HIGHER PER SPC SEC.
 310.3.4.(REVISE SPECS.)
  
 HOT WATER TO RESTROOMS SHALL BE 110
 DEGREES MAX.PER FLA.ENERGY CODE SEC.
 412.1ABCD.2.3.2.
  
 CONDENSATE DRAINS SHALL TERMINATE PER
 SEC.804.3 OF COUNTYWIDE AMENDMENTS TO
 STD.PLBG.CODE.
  
 DRAINS FROM SODA FOUNTAINS SHALL DRAIN
 TO GREASY WASTE SYSTEM.SPC 1004.1.