| Plan Review Notes For Permit 99091126 |
| Permit Number |
99091126 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CLEARLY SHOW LOCATION OF GREASE | | | INTERCEPTOR ON PLANS.SPC 104.2.1. | | | | | | CONTACT RODNEY COMPO AT CITY OF W.P.B. | | | REGIONAL WASTEWATER TREATMENT PLANT FOR | | | GREASE TRAP REQS.(561)835-7423. | | | | | | MULTIPLE CONDENSATE DRAINS SHALL BE | | | SIZED PER STD.MECH.CODE SEC.304.8.4. | | | | | | RECEPTACLES FOR INDIRECT WASTES SHALL BE | | | FLOOR DRAINS OR FLOOR SINKS PER SPC SEC. | | | 807. | | | | | | CLEARLY SHOW TERMINATION PT.OF TRENCH | | | DRAIN AT CAR WASH.SPC 104.2.1. | | | | | | VENTING FOR SANITARY SYSTEM SHALL COMPLY | | | W/SPC SEC.920.2. | | | | | | SPACING FOR COPPER TUBE SHALL BE 10'MAX. | | | FOR SIZES 2" AND HIGHER PER SPC SEC. | | | 310.3.4.(REVISE SPECS.) | | | | | | HOT WATER TO RESTROOMS SHALL BE 110 | | | DEGREES MAX.PER FLA.ENERGY CODE SEC. | | | 412.1ABCD.2.3.2. | | | | | | CONDENSATE DRAINS SHALL TERMINATE PER | | | SEC.804.3 OF COUNTYWIDE AMENDMENTS TO | | | STD.PLBG.CODE. | | | | | | DRAINS FROM SODA FOUNTAINS SHALL DRAIN | | | TO GREASY WASTE SYSTEM.SPC 1004.1. |
|