| Plan Review Notes For Permit 99091124 |
| Permit Number |
99091124 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)TWO WAY CLEANOUTS REQD.ENTERING AND | | | LEAVING EACH TANK.SEE 750 GAL RECLAIM | | | TANK.SPC SEC.710.4. | | | | | | 2)SIZE OF TANKS DO NOT MATCH APPROVED | | | PLANS.SEE RECLAIM TANK AND OIL/SAND INT. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 3)VENT SHALL RISE 6" ABOVE FLOOD LEVEL | | | OF INT.PRIOR TO OFFSETTING HORIZ.SPC | | | 906.2.1. | | | | | | 4)SUBMIT FULL SIZE BLUEPRINTS FOR REVIEW | | | THAT ARE SIGNED,DATED AND SEALED BY THE | | | DESIGN PROFESSIONAL OF RECORD.SPC SEC. | | | 104.2.3. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|