Plan Review Notes
Plan Review Notes For Permit 99091124
Permit Number 99091124
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:001)TWO WAY CLEANOUTS REQD.ENTERING AND
 LEAVING EACH TANK.SEE 750 GAL RECLAIM
 TANK.SPC SEC.710.4.
  
 2)SIZE OF TANKS DO NOT MATCH APPROVED
 PLANS.SEE RECLAIM TANK AND OIL/SAND INT.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 3)VENT SHALL RISE 6" ABOVE FLOOD LEVEL
 OF INT.PRIOR TO OFFSETTING HORIZ.SPC
 906.2.1.
  
 4)SUBMIT FULL SIZE BLUEPRINTS FOR REVIEW
 THAT ARE SIGNED,DATED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD.SPC SEC.
 104.2.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.