| 2001-01-08 00:00:00 | JOB SPECS.-PG.155-SEC.3.01(C)-HANGERS |
| | FOR COPPER TUBE 2" & LARGER SHALL COMPLY |
| | W/SPC SEC.310.3.4. |
| | |
| | CONTACT RODNEY COMPO AT CITY OF W.P.B. |
| | REGIONAL WASTEWATER TREATMENT PLANT FOR |
| | SIZE REQS.OF GREASE AND SAND/OIL INTER- |
| | CEPTORS.(561)835-7423. |
| | |
| | SHT.P-1-VENTS THRU ROOF CANNOT BE |
| | INCREASED PER SPC 905.2.(ONLY USED FOR |
| | FROST CLOSURE.) |
| | |
| | MULTIPLE CONDENSATE DRAINS SHALL BE |
| | SIZED PER STD.MECH.CODE SEC.304.8.4. |
| | |
| | RECEPTACLES FOR INDIRECT WASTES SHALL |
| | BE FLOOR DRAINS OR FLOOR SINKS PER SPC |
| | SEC.807. |
| | |
| | CLEARLY SHOW TERMINATION POINT OF TRENCH |
| | DRAIN AT CAR WASH.COMPLY W/SPC SEC.104.2 |
| | 1004.5,1004.6. |
| | |
| | VENTING FOR SANITARY SYSTEM SHALL COMPLY |
| | W/SPC SEC.920.2.(NOTE CAPACITY OF 1 1/2" |
| | VENT.) |
| | |
| | SHT.4 OF 8 SHOWS 2"WATER SERVICE AND SHT |
| | P2 SHOWS 1 1/2".CLARIFY.SPC 104.2.1. |
| | |
| | SIZE THE COOLER DRAINS ON SHT.P1.COMPLY |
| | W/SPC SEC.713.3,714.2. |
| | |
| | INDIRECT WASTES SHALL BE TRAPPED AND |
| | COMPLY W/SPC SEC.805.1.1,805.1.2. |
| | |
| | SUBMIT RISER DIAGRAMS FOR AIR/WATER |
| | SYSTEMS.SPC 104.2.1. |
| | |
| | SUBMIT MANUF.DATA FOR GREASE/OIL INTER. |
| | 104.2.2. |
| | |
| | DRAINS FROM SODA FOUNTAINS SHALL DRAIN |
| | TO GREASY WASTE SYSTEM.SPC 1004.1 |
| | |
| | HOT WATER TO RESTROOMS SHALL BE 110 |
| | DEGREES MAX PER FLA.ENERGY CODE SEC. |
| | 412.1 ABCD.2.3.2. |