Plan Review Notes
Plan Review Notes For Permit 99091124
Permit Number 99091124
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1) FAN SHUT DOWN REQUIRED FOR AHU 1,2&3
 BY DUCT SMOKE DETECTOR PER 1997 SMC 406
 2) NOTIFICATION BY HORN AND STROBE OF
 FAN SHUT DOWN REQUIRED BY NFPA 4-4.4.3
 3) ADDITIONAL MECHANICAL PERMITS REQUIRE
 FOR FUEL AND WALK IN COOLER