Plan Review Notes
Plan Review Notes For Permit 99091064
Permit Number 99091064
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO*****************
  
 *1)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 SUBMIT AIC RAING OF NEW EQUIPMENT TO
 INCLUDE MAINS AND BREAKERS. FIGURED
 FROM FAULT CURRENT CALCULATIONS.
 HAVE AIC RATING DRAWN ON PANEL SCHEDULE.
 *2)NOTE:PANEL SCHEDULE SHOW 150AMP
 MAIN BRKR. NEEDS TO BE 200 AMPS
 TO MATCH WHAT IS DRAWN ON RISER DIAGRAM.
 215-5
 *3)NOTE:NEED TO BOND STEEL OF NEW
 ADDITION TO GROUNDING ELECTRODE COND.
 ART;250-81
 *4)NOTE:LOAD CALCULATIONS SHOW 1700 SQ.
 FT. USED, YET SHEET A-1 SHOW SQ.FT.
 BEING 1872 SQ.FT. WITHOUT THE GARAGE.
 PLEASE REDO LOAD CALCULATIONS TO
 CORRELATE TO A-1
 *5)NOTE:AS PER ART:210-52 OUTLET SPACING
 TO MEET NEC.
 *6)NOTE:AS PER ART:210-52D A SEPARATE
 20 AMP CIRCUT IS REQ`D FOR BATH GFI REC.
 *7)NOTE: MASTER BEDROOM SHOWS SWITCH??
 DOES IT SERVE FOR MEANS OF EGRESS LIGHT-
 -ING WHICH IS REQ`D BY ART:210-70
 *8)NOTE: AS REQ`D BY 1993/1996 NFPA-72
 SEC.2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN RESIDENTIAL DWELLINGS OF NEW
 CONSTRUCTION.
  
 NOTE:ON NOTES ON YOUR PLANS YOU SHOW
 EACH APARTMENT???PLEASE REMOVE IF NOT
 NEEDED.
  
  
 NEED TO HAVE PLANS CORRECTED AND DRAWN
 OVER TO REFLECT CHANGES REQUESTED.
 PLEASE SUBMIT FOR REVIEW AND APPROVAL
 BEFORE FIRST ELECTRICAL INSPECTION IS
 CALLED IN.