2001-01-08 00:00:00CHECKLIST:
 1-TRUSS DRAWINGS:
 -THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING. TABLE 1606.2A SBC/97.
 -UPDATE ALL GENERAL DETAILS ACCORDING
 TO SBC 1997 OR ASCE 7-95.
 -CLARIFY WHY THERE ARE SOME DETAILS AND
 LETTERS SEALED BY DIFFERENT ENGINEERS.
 DATE OF DOCUMENTS TO BE THE DATE WHEN
 THEY ARE SEALED.
 -WHY IS LETTER FROM SIMPSON STRONG TIE
 SEALED BY ANOTHER ENGINEER.
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS "INSWING" TYPE AS SHOWN ON
 ARCHITECT'S PLANS.
 3-PRODUCT APPROVAL FOR GOLFCART DOOR
 DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT.
 4-ROYAL PALM ALUMINUM LETTER FROM THE
 MANAGER OF ENGINEERING TO BE SIGNED,
 SEALED AND DATED.
 5-PRODUCT APPROVAL FOR SLIDING GLASS
 DOORS WITH TRANSOM ABOVE ASSEMBLY:
 -PROVIDE PRODUCT APPROVAL FORM WITH ALL
 REQUIRED INFORMATION FROM MANUFACTURER
 ENGINEER AND PROFESSIONAL DESIGNER OF
 RECORD FOR SITE SPECIFIC INSTALLATION.
  
  
 NOTE:
 TO AVOID UNNECESSARY DELAYS, PLEASE TELL
 THE ARCHITECT AND ENGINEER TO PROVIDE
 ALL THE INFORMATION REQUIRED BY THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.