Plan Review Notes
Plan Review Notes For Permit 99091010
Permit Number 99091010
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************PROVISO******************
  
 1)NOTE:AS PER ARTS;110-9/215-5 PLEASE
 HAVE AIC RATING DRAWN ON PANEL SCHEDULE.
 AIC RATING FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:RISER DIAGRAM AND PANEL SCHEDULE
 DOESN`T MATCH, RISER SHOWS (MLO) AND
 PANEL SCHED. SHOWS (MCB).
  
 PLEASE HAVE THE ABOVE INFORMATION SUB-
 -MITTED FOR REVIEW AND APPROVAL BEFORE
 FIRST ELECTRICAL INSPECTION.