| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO****************** | | | | | | 1)NOTE:AS PER ARTS;110-9/215-5 PLEASE | | | HAVE AIC RATING DRAWN ON PANEL SCHEDULE. | | | AIC RATING FIGURED FROM FAULT CURRENT | | | CALCULATIONS. | | | 2)NOTE:RISER DIAGRAM AND PANEL SCHEDULE | | | DOESN`T MATCH, RISER SHOWS (MLO) AND | | | PANEL SCHED. SHOWS (MCB). | | | | | | PLEASE HAVE THE ABOVE INFORMATION SUB- | | | -MITTED FOR REVIEW AND APPROVAL BEFORE | | | FIRST ELECTRICAL INSPECTION. |
|