Plan Review Notes
Plan Review Notes For Permit 99091007
Permit Number 99091007
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00REVISION:
 ROYAL WALL SYSTEM IN LIEU OF CBS.
  
 CHECKLIST:
 1-FIRE RATED WALL AT ZERO LOT LINE DOES
 NOT MEET THE REQUIREMENTS FOR SECTIONS
 709.2.1.4.4 AND SECTION 709.2.1.4.5
 SBC 1997. (CALCS ARE INCORRECT).
 2-WHEN FINISHES ON CONCRETE WALLS ARE
 ASSUMED TO CONTRIBUTE TO THE TOTAL
 FIRE RESISTANCE OF THE WALL, THEN THE
 INSTALLATION REQUIREMENTS SHALL BE AS
 PER SECTION 709.3.1.6 SBC 1997.
 CODE SECTION 709.2.1.4.6 SBC 1997.
 3-PROVIDE COMPLETE DETAILS AND SPECS FOR
 CONCRETE PANELS WITH ROUND AND ARCHED
 OPENINGS. SEC. 104.2.2 CITY AMENDMENTS
 4-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) FOR INSULATION SHOWN.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 5-PROVIDE COPIES OF THE APPROVED DRAWING
 IN NOTED ON THE PRODUCT APPROVAL.
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 COLUMN AT REAR PORCH.
 SECTION 104.2.2 CITY AMENDMENTS.
  
 FROM PREVIOUS PROVISO DATED 10/29//99:
 1-PROVIDE FULL SET OF PRODUCT APPROVALS.
 2-UPDATE ALL ENGINEERED TRUSS DRAWINGS.
 CUT AND PASTE IS NOT ACCEPTABLE.
 3-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -PROVIDE DETAIL FOR INSTALLATION OF
 STORM PANELS AT FRONT WINDOWS. SEE
 EXTERIOR SILL DETAIL AND INSTALLATION
 SCHEDULE.