| 2001-01-08 00:00:00 | |
| | APPROVED WITH PROVISO: |
| | 1-PLEASE REVISE ALL ORIGINALS SHOWING |
| | ALL CORRECTIONS/CLARIFICATIONS. |
| | 2-PROVIDE SAFETY GLASS IN LIBRARY WINDOW |
| | SEC. 2405.2 SBC 1997. |
| | 3-ENTRY DOOR TO HAVE 32" MINIMUM CLEAR |
| | OPENING. TABLE 1004 SBC 1997. |
| | 4-ENGINEERED TRUSS DRAWINGS: |
| | -UPDATE ALL DETAILS. |
| | -UPDATE DESIGN CRITERIA |
| | -ENGINEER OF RECORD TO REVIEW ALL |
| | TRUSS DRAWINGS PRIOR TO SUBMITTAL. |
| | 5-REVISE DESIGN CERTIFICATION FOR WIND |
| | LOAD COMPLIANCE FORM. MEAN ROOF HEIGHT |
| | IS INCORRECT (21'-0" PLUS O MINUS). |
| | 6-SPECIFY SIZE OF CEILING FANS. TABLE |
| | 6-6 FLORIDA ENERGY CODE 1997 EDITION. |
| | CREDIT FOR CEILING FANS WAS TAKEN ON |
| | THE ENERGY CALCULATIONS. |
| | 7-PROVIDE FULL SET OF PRODUCT APPROVALS |
| | (MASTER PERMIT IS ON HOLD TILL ALL |
| | PLANS AND PRODUCT APPROVALS ARE |
| | COMPLETELY PREPARED). |
| | 8-STORM PANELS: |
| | PROVIDE A COMPLETE INSTALLATION |
| | SCHEDULE,AS PER CITY SAMPLE, ATTACHED, |
| | AND KEY PLAN. HIGHLIGHT SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR SCHED. |
| | 9-PROVIDE ATTIC ACCESS AT MAIN ROOF. |
| | SEC. 2309.6 SBC 1997. |
| | 10-PROVIDE COMPLETE SPECIFICATIONS FOR |
| | CEILINGS AT FRONT AND BACK PORCH. |
| | SEC. 104.2.2 CITY AMENDMENTS. |
| | 11-PROVIDE COMPLETE DETAILS AND SPECS |
| | FOR MOUNTING OF AHU'S. |
| | SEC. 104.2.2 CITY AMENDMENTS. |