2001-01-08 00:00:00************PROVISO********************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT,MAINS AND BRKRS,AS PER ARTS;
 110-9/215-5 AIC FIGURED FROM FAULT
 CURRENT CALCULATIONS.
 2)NOTE:GROUNDING ELECTRODE CONDUCTOR
 IS ONLY TO GO FROM FIRST MEANS OF DISC.
 TO PANEL.
 3)NOTE: AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE: AS PER ART: 210-63 RECEPT.REQ`D
 FOR A/C
  
 NEED TO SUBMIT FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION.