| Plan Review Notes For Permit 99091007 |
| Permit Number |
99091007 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************PROVISO******************** | | | | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT,MAINS AND BRKRS,AS PER ARTS; | | | 110-9/215-5 AIC FIGURED FROM FAULT | | | CURRENT CALCULATIONS. | | | 2)NOTE:GROUNDING ELECTRODE CONDUCTOR | | | IS ONLY TO GO FROM FIRST MEANS OF DISC. | | | TO PANEL. | | | 3)NOTE: AS PER ART:210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 4)NOTE: AS PER ART: 210-63 RECEPT.REQ`D | | | FOR A/C | | | | | | NEED TO SUBMIT FOR REVIEW AND APPROVAL | | | BEFORE FIRST ROUGH ELECTRICAL | | | INSPECTION. |
|