| 2001-01-08 00:00:00 | |
| | APPROVED WITH PROVISO: |
| | 1-PLEASE REVISE ALL ORIGINALS SHOWING |
| | ALL CORRECTIONS/CLARIFICATIONS. |
| | 2-PROVIDE SAFETY GLASS IN LIBRARY WINDOW |
| | SEC. 2405.2 SBC 1997. |
| | 3-REVISE ENTRY DOOR SIZE TO HAVE 32" MIN |
| | CLEAR OPENING. TABLE 1004 SBC 1997. |
| | 4-ENGINEERED TRUSS DRAWINGS: |
| | -UPDATE ALL DETAILS. |
| | -UPDATE DESIGN CRITERIA. |
| | -ENGINEER OF RECORD TO REVIEW ALL TRUSS |
| | DRAWINGS PRIOR TO SUBMITTAL. |
| | 5-REVISE DESIGN CERTIFICATION FOR WIND |
| | LOAD COMPLIANCE FORM. MEAN ROOF HEIGHT |
| | IS INCORRECT. (21'-0" PLUS OR MINUS). |
| | 6-SPECIFY SIZE OF CEILINGS FANS. TABLE |
| | 6-6 FLORIDA ENERGY CODE 1997 EDITION. |
| | CREDIT FOR CEILING FANS WAS TAKEN IN |
| | THE ENRGY CALCULATIONS. |
| | 7-PROVIDE FULL SET OF PRODUCT APPROVALS |
| | (MASTER PERMIT IS ON HOLD TILL ALL |
| | PLANS AND PRODUCT APPROVALS ARE |
| | PROPERLY CORRECTED). |
| | 8-STORM PANELS: |
| | PROVIDE A COMPLETE INSTALLATION |
| | SCHEDULE AS PER CITY SAMPLE ATTACHED |
| | AND KEY PLAN. |
| | HIGHLIGHT SPECIFIC MOUNTING CONDITIONS |
| | AND ANCHOR SCHEDULE. |
| | 9-PROVIDE ATTIC ACCESS AT MAIN ROOF. |
| | SEC. 2309.6 SBC 1997. |
| | 10-PROVIDE COMPLETE SPECIFICATIONS FOR |
| | CEILING AT FRONT AND BACK PORCHES. |
| | SEC. 104.2.2 CITY AMENDMENTS. |
| | 11-PROVIDE COMPLETE DETAILS AND SPECS |
| | FOR MOUNTING OF AHU'S. |
| | SEC. 104.2.2 CITY AMENDMENTS. |