| Plan Review Notes For Permit 99091004 |
| Permit Number |
99091004 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************PROVISO**************** | | | | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS AND BRANCH BREAKERS. | | | AIC RATING IS FIGURED FROM FAULT | | | CURRENT CALCULATIONS.AS PER ARTS:110-9/ | | | 215-5. | | | 2)NOTE:RISER DIAGRAM SHOWS EQUIPMENT | | | GROUND BEING INSTALLED FROM METER TO | | | MAIN DISCONNECT. EQUIPMENT GROUND IS | | | ONLY TO BE INSTALLED AFTER FIRST MEANS | | | OF DISC. | | | 3)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 4)NOTE:AS PER ART:210-52H OUTLET REQ`D | | | IN MASTER BEDROOM HALLWAY. | | | | | | PLEASE HAVE THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. |
|