Plan Review Notes
Plan Review Notes For Permit 99091003
Permit Number 99091003
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00 
 APPROVED WITH PROVISO:
 1-PROVIDE ATTIC ACCESS AT MAIN ROOF AND
 AT GUEST SUITE. SEC 2309.6 SBC 1997.
 2-PROVIDE PRODUCT APPROVAL FOR
 HORIZONTAL SLIDERS,ENTRY DOORS.
 3-CEILING FAN IN LIBRARY IS NOT OPTIONAL
 BECAUSE CREDIT WAS TAKEN FOR CEILING
 FANS IN THE ENERGY CALCULATIONS.
 REVISE PLANS AS REQUIRED.
 4-PROVIDE COMPLETE INSTALLATION SPECS
 FOR CEILINGS AT FRONT AND REAR PORCHES
 NOTE: FRONT CEILING CALLS FOR STUCCO
 CEILING AND REAR PORCH CALLS FOR
 DRYWALL CEILING. SEC 2504 SBC 1997.
 5-UPDATE ALL TRUSS DRAWINGS:
 -DESIGN CRITERIA TO BE EITHER SBC 1997
 OR ASCE 7-95. DESIGN CRITERIA MUST BE
 SPECIFIED ON ENGINEERED DRAWINGS.
 -TRUSS DRAWINGS TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
 -TRUSS LAYOUT TO BE SIGNED, SEALED AND
 DATED BY TRUSS ENGINEER.
 -PROVIDE TWO COPIES OF ENGINEERED
 DRAWINGS, SIGNED, SEALED AND DATED.
 -UPDATE ALL SUPPORTING DETAILS USING
 SBC 97 OR ASCE 7-95.
 6-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. MEAN
 ROOF HEIGHT AND BASIC VELOCITY
 PRESSURE ARE INCORRECT.
 TABLE 1606.2A SBC 1997.
 CLARIFY WHAT RESPONSIBILITY IS ROBERT
 AGSTEN, THE ENGINEER, ASSUMING.
 NONE OF THE DRAWINGS ARE SIGNED AND
 SEALED BY HIM, EXCEPT FOR THE DESIGN
 CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM.
 7-STORM PANELS:
 -PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN. HIGHLIGHT SPECIFIC MOUNTING
 CONDITIONS AND ANCHORS TO BE USED.