| 2001-01-08 00:00:00 | |
| | APPROVED WITH PROVISO: |
| | 1-PROVIDE ATTIC ACCESS AT MAIN ROOF AND |
| | GUEST SUITE. SEC 2309.6 SBC 1997. |
| | 2-PROVIDE PRODUCT APPROVAL FOR |
| | HORIZONTAL SLIDERS, ENTRY DOORS. |
| | 3-CEILING FAN IN LIBRARY IS NOT OPTIONAL |
| | BECAUSE CREDIT WAS TAKEN FOR CEILING |
| | FANS IN THE ENERGY CALCULATIONS.REVISE |
| | 4-PROVIDE COMPLETE INSTALLATION SPECS |
| | FOR CEILINGS AT FRONT AND REAR PORCHES |
| | NOTE: FRONT CEILING CALLS FOR STUCCO |
| | CEILING AND REAR PORCH CALLS FOR |
| | DRYWALL CEILING. SEC 2504 SBC 1997. |
| | 5-UPDATE ALL TRUSS DRAWINGS: |
| | -DESIGN CRITERIA TO BE EITHER SBC 1997 |
| | OR ASCE 7-95. IT MUST BE SPECIFIED ON |
| | ENGINEERED DRAWINGS. |
| | -TRUSS DRAWINGS TO BE REVIEWED BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL. |
| | TRUSS LAYOUT TO BE SIGNED, SEALED AND |
| | DATED BY TRUSS ENGINEER. |
| | -UPDATE ALL SUPPORTING DETAILS AND |
| | INFORMATION USING SBC 1997 OR ASCE7-95 |
| | 6-REVISE THE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM. MEAN |
| | ROOF HEIGHT AND BASIC VELOCITY |
| | PRESSURE ARE INCORRECT. SEE TABLE |
| | 1606.2A SBC 1997. |
| | CLARIFY WHAT RESPONSIBILITY IS ROBERT |
| | AGSTEN, THE ENGINEER, ASSUMING. NONE |
| | OF THE DRAWINGS ARE SIGNED AND SEALED |
| | BY HIM, EXCEPT FOR THE DESIGN |
| | COMPLIANCE FORM. |
| | 7-STORM PANELS: |
| | -PROVIDE INSTALLATION SCHEDULE AND KEY |
| | PLAN. HIGHLIGHT SPECIFIC MOUNTING |
| | CONDITIONS AND ANCHORS SPACING. |