2001-01-08 00:00:00SHT.27OU-1-SHOWS 8" HORIZONTAL STORM
 DRAIN SERVING 25,900 SQ.FT.OF ROOF AREA.
 8" IS INADEQUATE.COMPLY W/SPC SEC.1108.2
  
 SUBMIT COMPLETE DETAILS INCLUDING STORM
 RISER DIAGRAM SHOWING SIZE OF ROOF DRAIN
 AND SQ.FOOTAGE DRAINED BY EACH DRAIN.
 AND INDICATE SLOPE OF PIPE ON PLAN.
 COMPLY W/SPC 1108.1,1108.2
  
 PLANS SHOW DRAIN AT SCISSOR LIFT.SUBMIT
 DETAILS FOR DRAIN.SHOW TERMINATION POINT
 AND SIZE.(AN INTERCEPTOR MAY BE REQD.
 IF LIFT IS HYDRAULIC.)
  
 VENTS FOR INTERCEPTOR SHALL COMPLY W/SPC
 SEC.906.2.1.(MUST RISE 6" ABOVE FLOOD
 LEVEL RIM PRIOR TO OFFSETTING HORIZ.)
  
 STORM DRAINAGE CANNOT BE COMBINED W/
 SANITARY.(SEE DRAIN AT DUMPSTER.
 PROVISIONS SHALL BE MADE TO AVOID STORM
 WATER DRAINING ONTO PAD.)SPC 1106.3.
  
 VOID OLD REVISIONS IN PLANS.