Plan Review Notes
Plan Review Notes For Permit 99090901
Permit Number 99090901
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00SHT.270U-I REFERS TO SHTS.9363A-1 ETC.
 FOR EXISTING ROOF SCUPPERS.THESE DWGS.
 HAVE NOT BEEN SUBMITTED.CLARIFY.
  
 8" HORIZONTAL STORM DRAIN IS INADEQUATE
 TO CARRY PROJECTED ROOF AREA.SUBMIT
 COMPLETE DETAILS FOR THE STORM DRAINAGE
 SYSTEM.COMPLY W/TABLES 1108.1 1108.2.
 (PARAPET WALLS SHALL BE INCLUDED IN
 CALCULATIONS PER SPC SEC.1108.3)
  
 STORM DRAINAGE CANNOT BE COMBINED W/SAN.
 (SEE DRAIN AT DUMPSTER PAD.)SPC 1106.3
  
 PLANS SHOW DRAIN AT SCISSOR LIFT-SHOW
 TERMINATION PT.OF DRAIN.(INTERCEPTOR
 MAY BE REQD. IF LIFT IS OPERATED BY
 HYDRAULICS).SPC SEC.1004.1
  
 INDICATE SQUARE FOOTAGE OF ROOF DRAINED
 BY EACH ROOF DRAIN AND INDICATE SLOPE OF
 PIPE ON PLAN.
  
 VENTS FOR INTERCEPTOR SHALL COMPLY W/SPC
 SEC.906.2.1.(MUST RISE 6" ABOVE FLOOD
 LEVEL RIM PRIOR TO OFFSETTING HORIZ.)