2001-01-08 00:00:00PLANS SHOW DRAIN AT SCISSOR LIFT-SHOW
 TERMINATION PT.OF DRAIN.(MAY BE REQUIRED
 TO DRAIN TO INTERCEPTOR IF LIFT IS
 OPERATED BY HYDRAULICS.)SPC SEC.1004.1.
  
 SUBMIT DETAILS FOR SECONDARY ROOF DRAIN-
 AGE.COMPLY W/SPC SEC.1109.
  
 RAIN SENSOR REQD.ON IRRIGATION SYSTEM
 PER FLA.STATUTE 373.62.
  
 INDICATE SQUARE FOOTAGE OF ROOF DRAINED
 BY ROOF DRAIN AND INDICATE SLOPE OF PIPE
 COMPLY W/SPC TABLE 1108.1,1108.2.
  
 CONTACT RODNEY COMPO AT CITY OF W.P.B.
 REGIONAL WASTEWATER TREATMENT PLANT FOR
 REQS.OF GREASE INTERCEPTOR.(561)835-7423