Plan Review Notes
Plan Review Notes For Permit 99090901
Permit Number 99090901
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CORRECTED ON REVISION************
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2
 3)NOTE: CONDENSATE DRAIN LINE TO BE SIZE
 D IN ACCORDANCE WITH ACCEPTED ENGINEERIN
 G PRACTICE (INCREASE SIZE TO ACCOMIDATE
 ADDITIONAL UNITS)