| Plan Review Notes For Permit 99090853 |
| Permit Number |
99090853 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DISTANCE OF WATER CLOSET TRAP FROM IT'S | | | VENT SHALL NOT EXCEED 5 FT.PER COUNTY- | | | WIDE AMENDMENTS TO THE STANDARD PLBG. | | | CODE SEC.908.1 FOOTNOTE #2.(SEE WOMENS | | | TOILET ROOM.) | | | | | | WATER CLOSET AND HAND SINK NOT SHOWN ON | | | SANITARY RISER. | | | | | | OVER 4 FIXTURES CONNECTED TO 1/2" HOT | | | WATER PER COUNTYWIDE AMENDMENTS TO THE | | | STANDARD PLBG.CODE SEC.607.7 | | | | | | GAS SYSTEM SHALL BE SIZED FOR TOTAL OF | | | 825,000 BTU'S AND 80' IN LENGTH AS | | | SHOWN BY TOTAL DEVELOPED LENGTH OF CUT | | | SECTIONS OF PIPE.SGC TABLE 305.4(A). | | | | | | PLANS SHALL BE SIGNED AND SEALED.SPC | | | 104.2.3. | | | | | | SIZE THE GAS LINE IN ITS ENTIRETY.SGC | | | SEC.395.4. | | | | | | UNION SHALL BE INSTALLED DOWNSTREAM OF | | | EMERG.S.O.V. TO ALLOW FOR MAINTENANCE | | | AND REPLACEMENT. | | | | | | SANITARY SYSTEM DESIGN SHALL COMPLY W/ | | | COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE | | | SEC.911.1.1, OR SPC 914.1 FOR VENTING | | | OF BATTERY FIXTURES. |
|