Plan Review Notes
Plan Review Notes For Permit 99090853
Permit Number 99090853
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00DISTANCE OF WATER CLOSET TRAP FROM IT'S
 VENT SHALL NOT EXCEED 5 FT.PER COUNTY-
 WIDE AMENDMENTS TO THE STANDARD PLBG.
 CODE SEC.908.1 FOOTNOTE #2.(SEE WOMENS
 TOILET ROOM.)
  
 WATER CLOSET AND HAND SINK NOT SHOWN ON
 SANITARY RISER.
  
 OVER 4 FIXTURES CONNECTED TO 1/2" HOT
 WATER PER COUNTYWIDE AMENDMENTS TO THE
 STANDARD PLBG.CODE SEC.607.7
  
 GAS SYSTEM SHALL BE SIZED FOR TOTAL OF
 825,000 BTU'S AND 80' IN LENGTH AS
 SHOWN BY TOTAL DEVELOPED LENGTH OF CUT
 SECTIONS OF PIPE.SGC TABLE 305.4(A).
  
 PLANS SHALL BE SIGNED AND SEALED.SPC
 104.2.3.
  
 SIZE THE GAS LINE IN ITS ENTIRETY.SGC
 SEC.395.4.
  
 UNION SHALL BE INSTALLED DOWNSTREAM OF
 EMERG.S.O.V. TO ALLOW FOR MAINTENANCE
 AND REPLACEMENT.
  
 SANITARY SYSTEM DESIGN SHALL COMPLY W/
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.911.1.1, OR SPC 914.1 FOR VENTING
 OF BATTERY FIXTURES.