| Plan Review Notes For Permit 99090853 |
| Permit Number |
99090853 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | WHEELCHAIR TURNING SPACE IN HANDICAP | | | TOILET ROOMS SHALL COMPLY W/FACBC SEC. | | | 4.2.3. | | | | | | CLEARLY NOTE ALL NEW AND EXISTING PLBG. | | | ON THE PLANS.SPC 104.2.1. | | | | | | SUBMIT SANITARY,WATER AND GAS ISOMETRICS | | | FOR ALL NEW PLBG. WORK.SPC 104.2.1. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PROVIDE PERMANENT LADDER OR INSTALL EWH | | | ON FLOOR.SPC SEC.501.7. | | | | | | MIN.FIXTURE REQS.SHALL COMPLY W/SPC | | | TABLE 407.(SEE FOOTNOTE #17.) | | | | | | CLEAR FLOOR SPACE FOR URINAL SHALL | | | COMPLY W/FACBC SEC.4.18.3. | | | | | | FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPC 409.4.1.1. | | | | | | SUBMIT DETAIL OF GREASE TRAP.SPC 104.2.1 | | | | | | CONTACT ROD COMPO AT CITY OF W.P.B. | | | REGIONAL WASTEWATER TREATMENTPLANT FOR | | | GREASE TRAP REQS. (561)835-7423. | | | | | | GAS EQUIP SHALL BE APPROVED PER STD.GAS | | | CODE SEC.402.1,NFPA 54. | | | | | | ALL SHEETS TO BE SIGNED AND SEALED.SPC | | | SEC.104.2.3. |
|