Plan Review Notes
Plan Review Notes For Permit 99090853
Permit Number 99090853
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO*******************
 **********BEFORE ROUGH******************
  
 1)NOTE:AS PER ARTS:110-9/215-5 NEED TO
 SUBMIT AIC RATINGS OF MAINS AND BRANCH
 CIRCUTS.AIC RATINGS ARE FIGURED FROM
 FAULT CURRENT CACULATIONS.
 2)NOTE:AS PER ART;220-3 NEED LOAD CALCU-
 -LATIONS TO SHOW ALL LIGHTING LOADS AT
 125%. PLEASE REFIGURE LOAD CALCULATIONS
 FOR THE CONTINUOUS LOAD FACTOR.
 3)NOTE:AS PER ART:250-81 NEED TO SHOW
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 COLD WATER ALSO.
 4)NOTE:PLEASE SHOW LAYOUT OF ROOFTOP
 A/C EQUIPMENT AND RECEPT.AS PER 210-63
 5)NOTE:PLEASE SHOW MEANS OF EGRESS
 LIGHTING ON PLANS. AS REQ`D BY ART;210-
 -70.
 6)NOTE: PLEASE SEE ART:210-50D OF THE
 PALM BEACH COUNTY AMENDMENTS FOR OUTLET
 SPACING.EVRY 20` OF UNENCUMBERED WALL
 SPACE.
  
 NEED TO HAVE THE SUBMITTED FOR REVIEW
 AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.!!!!!