| Plan Review Notes For Permit 99090853 |
| Permit Number |
99090853 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | **********BEFORE ROUGH****************** | | | | | | 1)NOTE:AS PER ARTS:110-9/215-5 NEED TO | | | SUBMIT AIC RATINGS OF MAINS AND BRANCH | | | CIRCUTS.AIC RATINGS ARE FIGURED FROM | | | FAULT CURRENT CACULATIONS. | | | 2)NOTE:AS PER ART;220-3 NEED LOAD CALCU- | | | -LATIONS TO SHOW ALL LIGHTING LOADS AT | | | 125%. PLEASE REFIGURE LOAD CALCULATIONS | | | FOR THE CONTINUOUS LOAD FACTOR. | | | 3)NOTE:AS PER ART:250-81 NEED TO SHOW | | | GROUNDING ELECTRODE CONDUCTOR GOING TO | | | COLD WATER ALSO. | | | 4)NOTE:PLEASE SHOW LAYOUT OF ROOFTOP | | | A/C EQUIPMENT AND RECEPT.AS PER 210-63 | | | 5)NOTE:PLEASE SHOW MEANS OF EGRESS | | | LIGHTING ON PLANS. AS REQ`D BY ART;210- | | | -70. | | | 6)NOTE: PLEASE SEE ART:210-50D OF THE | | | PALM BEACH COUNTY AMENDMENTS FOR OUTLET | | | SPACING.EVRY 20` OF UNENCUMBERED WALL | | | SPACE. | | | | | | NEED TO HAVE THE SUBMITTED FOR REVIEW | | | AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN.!!!!! |
|