| Plan Review Notes For Permit 99090784 |
| Permit Number |
99090784 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)AC AND ELECTRICAL SERVICE IN SAME | | | SPACE SEE 110-16 | | | | | | 2)SHOW ALL WORK NEW AND EXISTING. | | | | | | 3)SHOW ALL BRANCH CIRCUIT NUMBERS ON | | | PLAN(HOW MANY OUTLETS ON A CKT.) | | | | | | 4)NO FAULT CURRENT CALCULATION 110-10 |
|