| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)LOAD CALCULKATION SHOWN IS FOR | | | RESIDENTIAL NOT COMMERCIAL | | | | | | 2)LOAD CALC. SHALL SHOW CONTINUOUS | | | LOAD FACTOR ON LIGHTING PER 220-10B | | | | | | 3)OUTLET SPACING IS NOT TO LOCAL CODE | | | IN OFFICE AREA 12' ON CENTER ALL | | | OTHER AREAS 20' ON CENTER ! | | | | | | 4)TRACK LIGHTING IS NOT SHOWN ON LOAD | | | CALCULATION410-102 | | | | | | 5)NO BRANCH CIRCUIT NUMBERS SHOWN ON | | | PLANS | | | | | | 6)NO PANEL SCHEDULES SHOWN | | | | | | 7)SUBMIT AIC CALCULKATION FOR SERVICE | | | AND PANELS110-9,10 | | | | | | 8)WHAT TYPE OF OCCUPANCY ARE THESE? | | | OFFICE SPACES REQUIRE 3.5 VA PER SQ. | | | FT. FOR LIGHTING PLUS CONTINOUS FAC. | | | | | | 9)SERVICE LOCATION NOT SHOWN!!!!!!!!! | | | | | | 10) A/C COMPRESSORS NOT SHOWN, ALSO NEED | | | GFI OUTLETS FOR SERVICE OF A/CS | | | | | | | | | APPROVED BY J LEAHY SEE PLANS FOR | | | PROVISO. |
|