| Plan Review Notes For Permit 99090717 |
| Permit Number |
99090717 |
|
| Review Stop |
P |
| Sequence Number |
11 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SHT.P-2-CONDENSATE DRAINS SHALL NOT BE | | | DIRECTLY CONNECTED TO THE STORM DRAINAGE | | | SYSTEM PER SPC SEC.804.3. | | | | | | SHT.P-2-NOTES BAR SINKS/LAVS CONNECTED | | | TO SANITARY SYSTEM.FIXTURES IN KITCHEN | | | AREA EXCEPT DISHWASHER SHALL DISCHARGE | | | INTO THE GREASY WASTE SYSTEM.SPC SEC. | | | 804.1.,1004.4. | | | | | | TWO WAY CLEANOUTS ARE REQD.ON THE INLET | | | AND OUTLET OF THE GREASE INTERCEPTORS. | | | SPC SEC.710.4. | | | | | | BRANCH LINES SHALL BE VALVED PER SPC | | | 610.4.2.(SEE NOTED AREAS ON PLANS.) | | | | | | SHT.P-4-NOTE #1-STATES DISHWASHER TO | | | DISCHARGE INTO SANITARY.REVISE NOTE. | | | DISHWASHER SHALL DISCHARGE TO SANITARY | | | PER CITY OF WEST PALM BEACH ORDINANCE. | | | | | | CHECK DIMENSIONS AND CORRESPONDING | | | CAPACITIES OF GREASE TRAPS.CAPACITY IN | | | GALS.AND DIMENSIONS DON'T CORRELATE. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
|