| Plan Review Notes For Permit 99090717 |
| Permit Number |
99090717 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SHT.P-1 NOTES BAR SINKS CONNECTED TO | | | SANITARY SYSTEM.SINKS SHALL CONNECT TO | | | GREASY WASTE SYSTEM PER SPC SEC.1004.4. | | | | | | FLOOR DRAINS ARE NOT PROPERLY VENTED. | | | COMPLY W/SPC SEC.901.2. | | | | | | CONTACT RODNEY COMPO AT CITY OF WEST | | | PALM BEACH REGIONAL WASTEWATER TREATMENT | | | PLANT FOR PROPER SIZINGOF GREASE TRAP. | | | (PHONE # 835-7423. | | | | | | CLEARLY SHOW LOCATION OF G/T ON PLANS. | | | AND DISTANCE FROM BUILDING.EXCAVATION | | | SHALL COMPLY W/SBC SEC.1803. | | | | | | SHT.P-2.NOTE #10-TYPE"M" COPPER NOT | | | PERMITTED U/G PER COUNTYWIDE AMENDMENTS | | | TO BUILDING SEC.611.2. | | | | | | HOSE BIBBS SHALL BE VALVED PER SPC SEC. | | | 610.4.1. | | | | | | SHT.G-1.-GAS PIPE SHALL NOT BE INSTALLED | | | UNDER BLDG.PER STD.GAS CODE SEC.308.3 |
|