| Plan Review Notes For Permit 99090704 |
| Permit Number |
99090704 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1- PG. E-2 SHOWS PANEL HA AS HAVING 60 | | | SPACES IT SHOULD BE NOTED THAT THIS | | | IS TWO 30 CIRCUIT PANELS. 384-16 | | | 2- PG. E-2,E-5,AND E-11 HAVE NO AIC | | | RATING SHOWN FOR BRANCH CIRCUITS. | | | MAIN AIC RATING IS SHOWN BUT NOT | | | THE BRANCH CIRCUIT RATINGS. 110-9 | | | 3- PG. E-4,E-7, AND E-10 SHOW OUTLETS | | | FOR SERVICING THE A/C EQUIPMENT ON | | | ROOFS.NOTE IT IS A LOCAL AMENDMENT | | | THAT THESE OUTLETS ARE FURTHER THAN | | | 25' AWAY!!210-63 | | | 4- PG.E-5 ELECTRIC ROOM ON 1ST SHOWS NO | | | OUTLET FOR SERVICING THE EQUIP. | | | 5- SUBMIT ALL INFORMATION REQUESTED | | | BEFORE 1ST ROUGH INSPECTION |
|